Technical Specifications
Design Life @25C (years)
16 years
Product Type Title
2V Telecom and Utility Cells
Product Group Title
PG 2V Series - 2V Long Life
Product Group
PG 2V Series
Product Group Information
Engineered with advanced AGM, the PG 2V series delivers strong durability and long service life, ensuring consistent performance in demanding standby power environments. With a thick plate design, these batteries provide reliable standby power for critical applications such as telecom, networking, and military systems.
Long Term Storage Information
PG 2V series batteries may be stored for up to 6 months at 25C (77 F) and then a freshening charge is required. For higher temperatures the time interval will be shorter
Operating Temperature Range Charge
−4°F (−20°C) to 104°F (40°C)
Operating Temperature Range Discharge
5°F (−15°C) to 122°F (50°C)
Operating Temperature Range Recommended
5°F (−15°C) to 104°F (40°C)
Dimensional Tolerances
+/- 0.08 in. (+/- 2mm) for length, width, and height dimensions
Additional Specifications
For the detailed technical specifications please refer to the model's technical document
Group Information
PG 2V series combines a special grid alloy, high-purity materials, and proven AGM technology to deliver low gassing, reduced self-discharge, and dependable long life.
Product Description
The PG-2V300 is part of our 2V Telecom and Utility Cells range. This 2.0V and 320.0Ah battery cell provides durability in light cyclic uses. Features include AGM Technology, Off Grid Capacity, SLA ABS Case, SLA Discharge Recovery, SLA Maintenance Free, and Thick Plate 10-12yr Design Life. These batteries are commonly used in Emergency Lighting, Fire Security, Solar, Telecomm, UPS, Utility, and Wind requiring demanding standby power. Backed by decades of expertise, Power-Sonic batteries are subject to stringent quality controls through each step of the manufacturing process to ensure compliance, performance consistency, and reliability.
Charging Description
Cycle Applications: Apply constant voltage charge at 2.35VPC – 2.45VPC (14.1 to 14.7 volts for 12V Monobloc) at 20°C. The initial charging current should be set at less than C/5 Amps. Switch to float charge when the current falls to a 3% capacity rate to avoid overcharging.
Stand-By or "Float" Service: Apply constant voltage charge of 2.25VPC – 2.30VPC (13.5 to 13.8 volts for 12V Monobloc) at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.
Temperature Compensation: Charging voltage for both cyclic and stand-by applications should be regulated in relation to ambient temperature. As temperature rises, charging voltage should be reduced to prevent overcharge and increased as the temperature falls to avoid undercharge.
For further charging information, including temperature compensation factors, see the Power-Sonic Technical Manual.
Voltage
2.0
Number of Series Cells
1.0
Stored Energy (Wh)
640.0
Rated Capacity 20hr
320.0
Rated Capacity 10hr
300.0
Rated Capacity 5hr
268.5
Rated Capacity 1hr
184.0
Capacity Voltage 20hr
1.8
Capacity Voltage 10hr
1.8
Capacity Current 10hr
30.0
Capacity Voltage 5hr
1.7
Capacity Voltage 1hr
1.6
Cycle Constant Voltage Range
2.33V - 2.45V
Float Constant Voltage Range
2.25V-2.30V-3mV/℃
Initial Charging Current (A)
96.0
Capacity Current 5hr
53.7
Capacity Current 1hr
184.0
Max Continuous Discharge Current (A)
2400.0
Internal Resistance (mΩ)
0.8
Capacity Current 20hr
16.0
Short Circuit Current (A)
3900.0
Constant Current Discharge Table
| Voltage | 15min | 20min | 30min | 45min | 1h | 1.5h | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60V/cell | 372.9 | 315.0 | 253.1 | 214.4 | 184.0 | 141.7 | 113.1 | 84.5 | 67.0 | 56.0 | 48.1 | 38.6 | 31.9 | 16.8 |
| 1.65V/cell | 357.5857 | 304.4 | 250.13879999999997 | 205.3 | 176.72849999999997 | 136.54919999999998 | 109.36019999999998 | 82.0705 | 65.3543 | 54.78079999999999 | 47.1 | 37.9639 | 31.418399999999995 | 16.615499999999997 |
| 1.67V/cell | 355.1 | 302.3 | 248.4 | 203.9 | 175.5 | 135.6 | 108.6 | 81.5 | 64.9 | 54.4 | 46.8 | 37.7 | 31.2 | 16.5 |
| 1.70V/cell | 343.0 | 292.2 | 241.7 | 199.4 | 171.9 | 133.2 | 106.8 | 80.3 | 64.0 | 53.7 | 46.3 | 37.3 | 30.9 | 16.4 |
| 1.75V/cell | 308.2 | 261.0 | 227.1 | 192.1 | 165.8 | 128.9 | 103.5 | 78.0 | 62.4 | 52.5 | 45.3 | 36.7 | 30.5 | 16.2 |
| 1.80V/cell | 279.4 | 247.6 | 217.0 | 184.6 | 159.9 | 124.7 | 100.4 | 76.0 | 60.9 | 51.3 | 44.4 | 36.0 | 30.0 | 16.0 |
| 1.85V/cell | 225.2 | 203.5 | 189.0 | 165.1 | 144.5 | 113.9 | 92.3 | 70.2 | 56.5 | 47.7 | 41.4 | 33.6 | 28.1 | 15.2 |
Constant Power Discharge Table
| Voltage | 15min | 20min | 30min | 45min | 1h | 1.5h | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60V/cell | 648.5 | 553.0 | 444.2 | 400.0 | 345.4 | 268.1 | 215.3 | 162.1 | 129.3 | 108.6 | 93.6 | 75.4 | 62.6 | 33.3 |
| 1.65V/cell | 628.5 | 539.3 | 439.9 | 384.4 | 332.5 | 258.8 | 208.2 | 157.3 | 125.8 | 105.8 | 91.5 | 73.9 | 61.4 | 32.8 |
| 1.67V/cell | 628.5 | 539.3 | 439.9 | 384.4 | 332.5 | 258.8 | 208.2 | 157.3 | 125.8 | 105.8 | 91.5 | 73.9 | 61.4 | 32.8 |
| 1.70V/cell | 611.3 | 524.6 | 432.3 | 377.9 | 327.3 | 255.1 | 205.5 | 155.4 | 124.4 | 104.8 | 90.5 | 73.3 | 60.9 | 32.5 |
| 1.75V/cell | 555.7 | 473.4 | 409.9 | 366.9 | 317.9 | 248.3 | 200.2 | 151.7 | 121.7 | 102.7 | 88.9 | 72.1 | 60.1 | 32.2 |
| 1.80V/cell | 509.1 | 453.5 | 395.2 | 355.3 | 308.7 | 241.7 | 195.3 | 148.4 | 119.2 | 100.8 | 87.3 | 71.0 | 59.3 | 31.8 |
| 1.85V/cell | 414.5 | 376.4 | 347.0 | 320.1 | 280.9 | 222.1 | 180.4 | 137.7 | 111.0 | 93.8 | 81.6 | 66.4 | 55.6 | 30.2 |
Charge Voltage (25C) - Equalization Charge
2.35V-2.40V/cell
-4mV/cell/℃
Charge Voltage (25C) - Float Charge
2.25V-2.30V/cell
-3mV/cell/℃
Recommended Charge Current (C rate)
0.1 C-0.3C
| Characteristic | 0203008418 |
|---|---|
| Terminal Type | M8 |
| VdS | ✗ No |
| Available in US | y |
| Available in EMEA | y |
| Terminal Image |
|
| SKU Battery | PG-2V300 FR M8 |
Case Material
ABS (UL94 HB or V-0 optional)
Product Image
Approximate Weight (kg)
18.6
Approximate Weight (lbs)
41.01
Length (in)
6.69
Length (mm)
170.0
Width (in)
5.91
Width (mm)
150.0
Height (in)
12.91
Height (mm)
328.0
Height Over Terminal (in)
13.7
Height Over Terminal (mm)
348.0
Dimensions
Emergency Lighting
Emergency Lighting
- Emergency lighting back up
Fire Security
Fire Security
- Fire and security panel
Solar
Solar
- Solar power generation
Telecomm
Telecomm
- Telecommunication installations
UPS
UPS
- Uninterruptable power supplies
Utility
Utility
- Utility installations
Wind
Wind
- Wind turbines
CE
CE
- CE marking confirms a product meets EU safety, health, and environmental protection standards for battery and energy systems.
Conflict Minerals
Conflict Minerals
- Conflict-free mineral certification ensuring ethical sourcing and transparent supply chain for responsible production.
Extended Minerals
Extended Minerals
- Extended mineral reporting meets global supply chain transparency standards for responsible and ethical sourcing practices.
IEC60896
IEC60896
- IEC 60896 standard ensures stationary lead-acid batteries meet safety, performance, and float charge application requirements.
ISO9001:2015
ISO9001:2015
- ISO 9001:2015 certification ensures consistent quality management and manufacturing standards for energy storage products.
PFAS
PFAS
- PFAS-free certification verifying environmentally responsible manufacturing of batteries and energy storage technologies.
Prop65
Prop65
- California Proposition 65 compliant, providing consumer safety through reduced chemical exposure in battery manufacturing.
REACH
REACH
- REACH compliant with EU chemical safety standards ensuring restricted substances are controlled in all battery components.
RoHS
RoHS
- RoHS compliance ensures restriction of hazardous substances in electrical, electronic, and battery-powered products.
SLA Transport
SLA Transport
- Sealed lead-acid batteries classified UN2800 non-spillable, certified safe for air, sea, and ground transport worldwide.
SVHC
SVHC
- SVHC compliant with EU REACH regulations for Substances of Very High Concern used in electrical and energy storage products.
TSCA
TSCA
- U.S. EPA TSCA compliance ensures toxic substances are regulated for safe manufacturing of batteries and electronic components.
UL 1989
UL 1989
- UL 1989 certified for valve-regulated and vented lead-acid batteries used in UPS, emergency, and backup power applications.
AGM Technology
AGM Technology
- Absorbent Glass Mat (AGM) technology for superior performance, service life, and reliability
Off Grid Capacity
Off Grid Capacity
- Wide offering of capacity range ideal for large capacity off-grid systems
SLA ABS Case
SLA ABS Case
- Rugged vibration and impact resistant ABS case and cover
SLA Discharge Recovery
SLA Discharge Recovery
- Excellent recovery from over discharge situations
SLA Maintenance Free
SLA Maintenance Free
- Proven valve regulated technology that guarantees safe operation without maintenance or refilling
Thick Plate 10-12yr Design Life
Thick Plate 10-12yr Design Life
- Thick plate design and efficient gas recombination yield a service life of 10 – 12 years in standby mode
Capacity Retention SLA
Capacity Retention SLA
- Shelf life of SLA at various temperatures
PS Cycle Life
PS Cycle Life
- Cycle life vs depth of discharge for the PS series
SLA Charging
SLA Charging
- Charging characteristics for SLA
SLA Float Life 10YR
SLA Float Life 10YR
- 10 year float life vs. temperature for SLA
CE IEC60896
Conflict Minerals Reporting Template (CMRT)
Extended Minerals
IMDG IATA Statement
Material Safety Data Sheet (MSDS) SLA AGM
PFAS
Product Warranty -Lead Acid
Prop 65
REACH
RoHS
SDS SLA AGM
SVHC
TSCA