PGFT-12V75 FR
Terminal Types:
M6
ABS (UL94 HB or V-0 optional)
Technical Specifications
Design Life @25C (years)
12 years
Product Type Title
Front Terminal AGM
Product Group Title
PG FT Series - Front Terminal
Product Group
PG FT Series
Product Group Information
Front terminal AGM batteries simplify installation and maintenance in telecom and UPS racks. High energy density and robust grid design enable reliable backup with streamlined service access for telecom and data center applications.
Long Term Storage Information
PGFT series batteries may be stored for up to 6 months at 25C (77 F) and then a freshening charge is required. For higher temperatures the time interval will be shorter
Operating Temperature Range Charge
−4°F (−20°C) to 104°F (40°C)
Operating Temperature Range Discharge
5°F (−15°C) to 122°F (50°C)
Operating Temperature Range Recommended
5°F (−15°C) to 104°F (40°C)
Dimensional Tolerances
+/- 0.08 in. (+/- 2mm) for length, width, and height dimensions
Additional Specifications
For the detailed technical specifications please refer to the model's technical document
Group Information
Built with front access terminals for easy service and compact footprints for high-density racks, these batteries offer low internal resistance for high-rate discharge and reliable backup power.
Product Description
The PGFT-12V75 is part of our Front Terminal AGM range. This 12.0V and 80.0Ah battery provides a space efficient design and simplified installation. Features include AGM Technology, Front Terminal, Long Shelf Life, Power Volume Ratio, SLA ABS Case, SLA Maintenance Free, and Thick Plate 10-12yr Design Life. These batteries are commonly used in Edge Data Center, Emergency Lighting, Telecomm, UPS, and Utility requiring long service life and high-rate discharge capability. Backed by decades of expertise, Power-Sonic batteries are subject to stringent quality controls through each step of the manufacturing process to ensure compliance, performance consistency, and reliability.
Charging Description
Cycle Applications: Apply constant voltage charge at 2.35VPC – 2.45VPC (14.1 to 14.7 volts for 12V Monobloc) at 20°C. The initial charging current should be set at less than C/5 Amps. Switch to float charge when the current falls to a 3% capacity rate to avoid overcharging.
Stand-By or "Float" Service: Apply constant voltage charge of 2.25VPC – 2.30VPC (13.5 to 13.8 volts for 12V Monobloc) at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.
Temperature Compensation: Charging voltage for both cyclic and stand-by applications should be regulated in relation to ambient temperature. As temperature rises, charging voltage should be reduced to prevent overcharge and increased as the temperature falls to avoid undercharge.
For further charging information, including temperature compensation factors, see the Power-Sonic Technical Manual.
Voltage
12.0
Number of Series Cells
6.0
Stored Energy (Wh)
960.0
Rated Capacity 20hr
80.0
Rated Capacity 10hr
75.0
Rated Capacity 5hr
67.0
Rated Capacity 1hr
50.3
Capacity Voltage 20hr
10.8
Capacity Voltage 10hr
10.8
Capacity Current 10hr
7.5
Capacity Voltage 5hr
10.2
Capacity Voltage 1hr
9.6
Cycle Constant Voltage Range
14.00V – 14.70V
Float Constant Voltage Range
13.50V-13.80V-18mV/℃
Initial Charging Current (A)
24.0
Capacity Current 5hr
13.4
Capacity Current 1hr
50.3
Max Continuous Discharge Current (A)
700.0
Internal Resistance (mΩ)
5.0
Capacity Current 20hr
4.0
Short Circuit Current (A)
1725.0
Recommended Chargers
PSC-126000ACX
Constant Current Discharge Table
| Voltage | 15min | 20min | 30min | 45min | 1h | 1.5h | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60V/cell | 140.7 | 116.6 | 87.3 | 63.8 | 50.3 | 36.2 | 29.1 | 21.5 | 16.9 | 14.0 | 11.7 | 9.65 | 7.97 | 4.18 |
| 1.65V/cell | 137.8 | 114.5 | 86.3 | 63.2 | 48.6 | 35.1 | 28.3 | 21.1 | 16.5 | 13.7 | 11.63 | 6.45 | 7.84 | 4.12 |
| 1.67V/cell | 136.8 | 113.9 | 85.5 | 62.7 | 48.0 | 34.6 | 27.9 | 20.8 | 16.4 | 13.6 | 11.6 | 9.42 | 7.8 | 4.11 |
| 1.70V/cell | 133.8 | 111.6 | 83.9 | 61.2 | 47.0 | 34.0 | 27.5 | 20.5 | 16.1 | 13.4 | 11.5 | 9.33 | 7.74 | 4.08 |
| 1.75V/cell | 127.8 | 108.0 | 81.8 | 59.9 | 45.4 | 32.9 | 26.6 | 19.9 | 15.8 | 13.1 | 11.4 | 9.16 | 7.62 | 4.03 |
| 1.80V/cell | 120.9 | 103.5 | 78.5 | 57.9 | 43.7 | 31.8 | 25.8 | 19.4 | 15.4 | 12.8 | 11.3 | 9.0 | 7.5 | 4.0 |
| 1.85V/cell | 111.6 | 94.5 | 72.8 | 54.4 | 39.5 | 29.0 | 23.7 | 17.9 | 14.3 | 11.9 | 10.8 | 8.41 | 7.03 | 3.77 |
Constant Power Discharge Table
| Voltage | 15min | 20min | 30min | 45min | 1h | 1.5h | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60V/cell | 255.9 | 214.7 | 163.3 | 120.8 | 94.5 | 68.4 | 55.3 | 41.3 | 32.6 | 27.1 | 23.4 | 18.9 | 15.6 | 8.28 |
| 1.65V/cell | 253.6 | 213.5 | 162.4 | 120.0 | 91.3 | 66.4 | 53.9 | 41.3 | 31.9 | 26.7 | 23.3 | 18.6 | 15.5 | 8.16 |
| 1.67V/cell | 253.0 | 212.7 | 161.7 | 119.9 | 90.9 | 66.0 | 53.5 | 40.1 | 31.7 | 26.5 | 23.2 | 18.5 | 15.4 | 8.14 |
| 1.70V/cell | 251.1 | 211.3 | 160.5 | 118.2 | 89.5 | 65.0 | 52.8 | 39.6 | 31.4 | 26.2 | 23.1 | 18.3 | 15.2 | 8.09 |
| 1.75V/cell | 242.7 | 206.6 | 157.9 | 116.6 | 86.9 | 63.2 | 51.4 | 38.6 | 30.7 | 25.7 | 22.9 | 18.0 | 15.0 | 7.99 |
| 1.80V/cell | 231.0 | 199.0 | 152.3 | 113.1 | 84.4 | 61.6 | 50.2 | 37.8 | 30.1 | 25.2 | 22.6 | 17.7 | 14.8 | 7.9 |
| 1.85V/cell | 214.3 | 182.7 | 141.7 | 106.7 | 76.8 | 56.5 | 46.4 | 35.1 | 28.0 | 23.5 | 21.7 | 16.6 | 13.9 | 7.49 |
Nominal Power W/Cell 15min Voltage
9.6
Charge Voltage (25C) - Equalization Charge
2.40V-2.45V/cell-4mV/cell/℃
Charge Voltage (25C) - Cycle Use
2.35V-2.40V/cell
-4mV/cell/℃
Charge Voltage (25C) - Float Charge
2.25V-2.30V/cell
-3mV/cell/℃
Recommended Charge Current (C rate)
0.1 C-0.3C
| Characteristic | 1207508416 |
|---|---|
| Terminal Type | M6 |
| VdS | ✗ No |
| Available in US | y |
| Available in EMEA | y |
| Terminal Image |
|
| SKU Battery | PGFT-12V75 FR M6 |
Case Material
ABS (UL94 HB or V-0 optional)
Product Image
Approximate Weight (kg)
26.0
Approximate Weight (lbs)
57.32
Length (in)
22.2
Length (mm)
564.0
Width (in)
4.49
Width (mm)
114.0
Height (in)
7.36
Height (mm)
187.0
Height Over Terminal (in)
7.36
Height Over Terminal (mm)
187.0
Dimensions
Edge Data Center
Edge Data Center
- Data center back up
Emergency Lighting
Emergency Lighting
- Emergency lighting back up
Telecomm
Telecomm
- Telecommunication installations
UPS
UPS
- Uninterruptable power supplies
Utility
Utility
- Utility installations
CE
CE
- CE marking confirms a product meets EU safety, health, and environmental protection standards for battery and energy systems.
Conflict Minerals
Conflict Minerals
- Conflict-free mineral certification ensuring ethical sourcing and transparent supply chain for responsible production.
Extended Minerals
Extended Minerals
- Extended mineral reporting meets global supply chain transparency standards for responsible and ethical sourcing practices.
IEC60896
IEC60896
- IEC 60896 standard ensures stationary lead-acid batteries meet safety, performance, and float charge application requirements.
ISO9001:2015
ISO9001:2015
- ISO 9001:2015 certification ensures consistent quality management and manufacturing standards for energy storage products.
PFAS
PFAS
- PFAS-free certification verifying environmentally responsible manufacturing of batteries and energy storage technologies.
Prop65
Prop65
- California Proposition 65 compliant, providing consumer safety through reduced chemical exposure in battery manufacturing.
REACH
REACH
- REACH compliant with EU chemical safety standards ensuring restricted substances are controlled in all battery components.
RoHS
RoHS
- RoHS compliance ensures restriction of hazardous substances in electrical, electronic, and battery-powered products.
SLA Transport
SLA Transport
- Sealed lead-acid batteries classified UN2800 non-spillable, certified safe for air, sea, and ground transport worldwide.
SVHC
SVHC
- SVHC compliant with EU REACH regulations for Substances of Very High Concern used in electrical and energy storage products.
TSCA
TSCA
- U.S. EPA TSCA compliance ensures toxic substances are regulated for safe manufacturing of batteries and electronic components.
UL 1989
UL 1989
- UL 1989 certified for valve-regulated and vented lead-acid batteries used in UPS, emergency, and backup power applications.
AGM Technology
AGM Technology
- Absorbent Glass Mat (AGM) technology for superior performance, service life, and reliability
Front Terminal
Front Terminal
- Front terminal design suited for 19" & 21" cabinets
Long Shelf Life
Long Shelf Life
- Long shelf life with low self-discharge
Power Volume Ratio
Power Volume Ratio
- Excellent power to volume ratio yielding high energy density
SLA ABS Case
SLA ABS Case
- Rugged vibration and impact resistant ABS case and cover
SLA Maintenance Free
SLA Maintenance Free
- Proven valve regulated technology that guarantees safe operation without maintenance or refilling
Thick Plate 10-12yr Design Life
Thick Plate 10-12yr Design Life
- Thick plate design and efficient gas recombination yield a service life of 10 – 12 years in standby mode
Capacity Retention SLA
Capacity Retention SLA
- Shelf life of SLA at various temperatures
PS Cycle Life
PS Cycle Life
- Cycle life vs depth of discharge for the PS series
SLA Charging
SLA Charging
- Charging characteristics for SLA
SLA Float Life 10YR
SLA Float Life 10YR
- 10 year float life vs. temperature for SLA
CE IEC60896
Conflict Minerals Reporting Template (CMRT)
Extended Minerals
IMDG IATA Statement
Material Safety Data Sheet (MSDS) SLA AGM
PFAS
Product Warranty -Lead Acid
Prop 65
REACH
RoHS
SDS SLA AGM
SVHC
TSCA