PSS-2V900

Terminal Types: M8

ABS Plastic Rated to UL94:HB

No product image available

Technical Specifications

Design Life @25C (years)
15 years in standby
Product Type Title
2V High Capacity
Product Group Title
PSS-2V Series - Long Life Standby
Product Group
PSS-2V Series
Product Group Information
High-capacity 2V VRLA cells designed for long design life in critical power and energy storage applications. Specifically designed for strong resilience to high temperatures with greater reliability. Designed for large-scale installations, they ensure secure, uninterrupted power when consistency is critical.
Long Term Storage Information
PSS series batteries may be stored for up to 6 months at 25C (77 F) and then a freshening charge is required. For higher temperatures the time interval will be shorter
Operating Temperature Range Charge
5°F (-15°C) to 104°F (40°C)
Operating Temperature Range Discharge
-4°F (-20°C) to 122°F (50°C)
Dimensional Tolerances
+/- 0.08 in. (+/- 2mm) for length, width, and height dimensions
Additional Specifications
For the detailed technical specifications please refer to the model's technical document
Group Information
These high-capacity 2V SLA batteries are built for demanding backup and energy storage systems, providing stable performance, exceptional longevity, and reliable operation even under elevated temperatures.
Product Description
The PSS-2V900 is part of our 2V High Capacity range. This 2.0V and 848.0Ah battery provides resilience to high temperatures in demanding scenarios. Features include OPZV/PSS Overcharge Endurance, SLA ABS Case, SLA Discharge Recovery, Superior Cyclic, and Thick Plate 10-12yr Design Life. These batteries are commonly used in Signaling (Air,Rail,Sea), Solar, Telecomm, UPS, Utility, and Wind requiring stable performance in large scale installations. Backed by decades of expertise, Power-Sonic batteries are subject to stringent quality controls through each step of the manufacturing process to ensure compliance, performance consistency, and reliability.
Charging Description
Cycle Applications: Apply constant voltage charge at 2.35VPC – 2.45VPC (14.1 to 14.7 volts for 12V Monobloc) at 20°C. The initial charging current should be set at less than C/5 Amps. Switch to float charge when the current falls to a 3% capacity rate to avoid overcharging. Stand-By or "Float" Service: Apply constant voltage charge of 2.25VPC – 2.30VPC (13.5 to 13.8 volts for 12V Monobloc) at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Temperature Compensation: Charging voltage for both cyclic and stand-by applications should be regulated in relation to ambient temperature. As temperature rises, charging voltage should be reduced to prevent overcharge and increased as the temperature falls to avoid undercharge. For further charging information, including temperature compensation factors, see the Power-Sonic Technical Manual.
Voltage
2.0
Number of Series Cells
1.0
Stored Energy (Wh)
1696.0
Rated Capacity 20hr
848.0
Rated Capacity 10hr
800.0
Rated Capacity 5hr
716.0
Rated Capacity 1hr
490.8
Capacity Voltage 20hr
1.8
Capacity Voltage 10hr
1.8
Capacity Current 10hr
80.0
Capacity Voltage 5hr
1.7
Capacity Voltage 1hr
1.6
Cycle Constant Voltage Range
2.33V - 2.45V
Float Constant Voltage Range
2.25V - 2.30V
Initial Charging Current (A)
212.0
Capacity Current 5hr
143.2
Capacity Current 1hr
490.8
Max Continuous Discharge Current (A)
6400.0
Internal Resistance (mΩ)
0.4
Capacity Current 20hr
42.4
Short Circuit Current (A)
8800.0
Constant Current Discharge Table
Voltage15min20min30min45min1h1.5h2h3h4h5h6h8h10h20h
1.60V/cell994.7840.2674.9571.7490.8377.8301.6225.3178.7149.4128.4102.985.044.6
1.65V/cell953.6289999999999811.9667.2382547.5471.27599999999995364.1312291.6272218.8211174.21099999999998146.015125.8101.2034999999999983.782444.10659999999999
1.67V/cell947.0806.3662.6543.7468.0361.6289.6217.3173.0145.0124.9100.583.243.8
1.70V/cell914.9779.3644.7531.7458.4355.2284.8214.1170.6143.2123.499.582.543.5
1.75V/cell822.1696.2605.6512.3442.2343.6276.0208.0166.4140.0120.897.781.242.9
1.80V/cell745.4660.4578.8492.3426.4332.4267.8202.6162.3136.9118.396.080.042.4
1.85V/cell600.5542.9504.0440.2385.3303.8246.1187.2150.6127.1110.389.775.040.2
Constant Power Discharge Table
Voltage15min20min30min45min1h1.5h2h3h4h5h6h8h10h20h
1.60V/cell1729.61475.11184.61066.6921.1714.9574.0432.3344.8289.6249.7201.2166.888.3
1.65V/cell1676.41438.51173.21025.1886.7690.0555.1419.4335.4282.2243.9197.1163.886.8
1.67V/cell1676.41438.51173.21025.1886.7690.0555.1419.4335.4282.2243.9197.1163.886.8
1.70V/cell1630.31399.21152.91007.6872.8680.4547.9414.3331.6279.3241.4195.4162.586.2
1.75V/cell1481.91262.71093.1978.5847.7662.1533.7404.4324.6273.9236.9192.4160.385.2
1.80V/cell1358.01209.61053.8947.5823.3644.5520.7395.6317.9268.7232.7189.3158.184.2
1.85V/cell1105.71004.1925.5853.6749.0592.4481.0367.1296.0250.2217.5177.2148.479.9
Recommended Charge Current (C rate)
106.0 - 353.3
Characteristic 0209008413
Terminal Type M8
VdS ✗ No
Available in US y
Available in EMEA y
Terminal Image Terminal Image
Case Material
ABS Plastic Rated to UL94:HB
Approximate Weight (kg)
50.4
Approximate Weight (lbs)
111.11
Length (in)
16.14
Length (mm)
410.0
Width (in)
6.89
Width (mm)
175.0
Height (in)
12.99
Height (mm)
330.0
Height Over Terminal (in)
13.78
Height Over Terminal (mm)
350.0
Signaling (Air,Rail,Sea)
Signaling (Air,Rail,Sea) - Signaling devices used in Air, Rail and Sea
Solar
Solar - Solar power generation
Telecomm
Telecomm - Telecommunication installations
UPS
UPS - Uninterruptable power supplies
Utility
Utility - Utility installations
Wind
Wind - Wind turbines
IEC60896
IEC60896 - IEC 60896 standard ensures stationary lead-acid batteries meet safety, performance, and float charge application requirements.
ISO9001:2015
ISO9001:2015 - ISO 9001:2015 certification ensures consistent quality management and manufacturing standards for energy storage products.
SLA Transport
SLA Transport - Sealed lead-acid batteries classified UN2800 non-spillable, certified safe for air, sea, and ground transport worldwide.
UL Recognized
UL Recognized - UL Recognized mark certifies safety-tested components for electrical reliability in battery and energy storage systems.
OPZV/PSS Overcharge Endurance
OPZV/PSS Overcharge Endurance - Enhanced overcharge endurance for increased safety
SLA ABS Case
SLA ABS Case - Rugged vibration and impact resistant ABS case and cover
SLA Discharge Recovery
SLA Discharge Recovery - Excellent recovery from over discharge situations
Superior Cyclic
Superior Cyclic - Superior cyclic performance
Thick Plate 10-12yr Design Life
Thick Plate 10-12yr Design Life - Thick plate design and efficient gas recombination yield a service life of 10 – 12 years in standby mode
Capacity Retention SLA
Capacity Retention SLA - Shelf life of SLA at various temperatures
PS Cycle Life
PS Cycle Life - Cycle life vs depth of discharge for the PS series
SLA Charging
SLA Charging - Charging characteristics for SLA
SLA Float Life 10YR
SLA Float Life 10YR - 10 year float life vs. temperature for SLA